Series 212 - Weather-Proof Differential Pressure Transmitter
$0.00
SKU
Series 212
The Series 212 Weatherproof Differential Pressure Transmitter can accurately measure positive, negative, or differential pressure and send a corresponding 4-20 mA or 0-10 V output signal. The Series 212 Weatherproof Differential Pressure Transmitter is designed with an IP 65 enclosure and can be easily mounted to any flat surface. The Series 212 is not position sensitive and can be mounted in any orientation without compromising accuracy. The compact, lightweight design makes installation simple and easy.
- Maximum Pressure:
- Ranges ≤ 5 PSI (35 kPa) = 15 PSI (100kPa) Max
Ranges > 5 PSI (35 kPa) = 30 PSI (200kPa) Max - Media compatibility:
- Air and compatible non-combustible, non-corrosive gases
- Accuracy:
- Ranges ≤ 4" w.c. (1kPa) 1.0%
Ranges ≥ 5" w.c. (1.25kPa) 0.25% - Temperature Ranges:
- Compensated: 15° to 120°F (-10° to 50°C)
Operating: -10° to 155°F (-25° to 70°C) - Thermal Effect:
- +/- 0.028% FS/°F (+/- 0.50% FS/°C)
- Stability:
- +/- 0.25% FS/year
- Output Signal:
- 4-20 mA, 2-wire or 0 - 10 V
- Loop Resistance:
- 250 Ω @ 24 VDC
- Power Supply:
- 12-30 VDC
- Enclosure Rating:
- IP 65
- Electrical Connections:
- screw terminals
- Electrical Entry:
- PG7 Cable Gland
- Process Connection:
- Barbed fittings for 3/16” flexible tubing
- Agency Approvals:
- CE
Model |
Pressure Range | Accuracy |
212-D001I-1 | 0-1" | 1% |
212-D002I-1 | 0-2" | 1% |
212-D004I-1 | 0-4" | 1% |
212-D006I-3 | 0-6" | 0.25% |
212-D010I-3 | 0-10" | 0.25% |
212-D020I-3 | 0-20" | 0.25% |
212-D040I-3 | 0-40" | 0.25% |
212-D005P-3 | 0-5 PSI | 0.25% |
212-D010P-3 | 0-10 PSI | 0.25% |
212-D015P-3 | 0-15 PSI | 0.25% |
212-D250A-1 | 0-250 Pa | 1% |
212-D500A-1 | 0-500 Pa | 1% |
212-D001K-1 | 0-1 kPa | 1% |
212-D002K-3 | 0-2 kPa | 0.25% |
212-D003K-3 | 0-3 kPa | 0.25% |
212-D005K-3 | 0-5 kPa | 0.25% |
212-D010K-3 | 0-10 kPa | 0.25% |
212-D025K-3 | 0-25 kPa | 0.25% |
212-D050K-3 | 0-50 kPa | 0.25% |
212-D100K-3 | 0-100 kPa | 0.25% |
*For 0-10 V output, add -V to the end of the part number. Consult factory for other calibration ranges including zero center ranges.